65NT_U33H1_E100
Domestic hot water for the DFAB Unit is provided by a heat pump boiler.
On the evaporator side, the heat pump boiler is connected to the return flow of the heating network of the DFAB Unit. The condensation heat exchanger is designed as a spiral pipe and transfers the heat directly in the boiler to the domestic hot water. The heat pump boiler is a prototype of the Nussbaum company. The heat pump boiler is located in the entrance area room no. 370 in a wall cabinet.

Facts & Figures
- Description: Domestic hot water heat pump
- Manufacturer: Nussbaum CTA
- Type: Prototype
- Commissioning: February 2019
- Dimensions H x W x D: 2150 x 600 x 600 mm
- Voltage/Frequency: 230 / 50 V / Hz
- WP Power consumption el.: 600 W
- WP Power output th.: 2800 W
- Electric auxiliary heating: 2500 W
- COP W25/W55: 4.7
- External fuse: 13 A
- Refrigerant R134a: 1 kg
- Minimum volume flow source side: 0.3 m3/h
- Minimum source temperature: 20 °C
- Maximum source temperature: 40 °C
- Storage content: 191 l
- Maximum operating pressure: 6 bar
- Maximum hot water temperature: 60 °C